Critec Range
The Critec range includes a variety of surge protectors, filters, diverters, arresters, suppressors & other protection devices for power & data lines.
The Critec surge protection range consists of a wide variety of surge protectors, diverters, arresters, suppressors, filters and a number of other protection devices which are used in power and data lines. The Critec range is developed and designed using a 6 point plan of protection agaisnt direct spikes and surges for power and data lines, making it ideal for use in the telecommunications industry. Below is a table outlining specifications for the Novaris surge protection range. For more detailed specifications, download the Critec Surge Protection Range document.
Critec Range Technical Description
Imax = Maximum Discharge Current (8/20µs) [unless stated otherwise]
Up = Voltage Protection Level – @ 3kA (8/20µs) [unless stated otherwise]
Uc = Maximum continuous operating voltage
Iimp= Maximum impulse current (10/350µs) [unless stated otherwise]
Iload=Maximum load current
Model
|
Imax / Iimp / Iline
|
Up
|
Uc
|
Phase/Pole
|
SEP400 – Service Entrance Premium
|
100kA
|
400 – 1560V
|
170 – 400V
|
3 Phase
|
SES200 – Service Entrance Standard
|
800 – 100kA
|
400 – 2000V
|
170 – 528V
|
1 & 3 Phase
|
SES65 – Service Entrance Standard
|
65kA
|
400 – 520V
|
150V
|
1 Phase
|
TDS MT – Transient Discriminating MOVTEC
|
200kA (MT)
40kA L-N & L-G (MTU)
20kA N-G (MTU)
|
330 – 1500V
|
170 – 528V
|
|
TDX 150 Series – Transient Discriminating Panel Protectors
|
75kA
|
400 – 1640V
|
170 – 830V
|
1 & 3 Phase
|
TDX 100 Series
|
50kA
|
400 – 1400V
|
70 – 830V
|
1 & 3 Phase
|
TDX 50 Series
|
25kA
|
400 – 1660V
|
10 – 830V
|
1 & 3 Phase
|
TDS MPM – TD Protection Module
|
100 – 130kA
|
0.75 – 2.3kV
|
400/692V
|
3 Phase
|
TSG SRF – Triggered Spark Gap Surge Reduction Filters
|
130kA / Iimp=50kA
|
262 – 413V
|
175V
|
1 Phase
|
130kA / Iimp=50kA
|
210 – 500V
|
275/476V
|
3 Phase
|
|
SGD/TSG – Surge Gap Diverter/TSG
|
130 – 140kA / Iimp=50/100kA
|
0.6 – 20kA
|
150 – 440V
|
|
DDI – DIN Decoupling Inductor
|
Iline=35 – 63A
|
500VAC
200VDC
|
||
DSD1150 – DIN Surge Diverter
|
150kA / Iimp= 25kA
|
0.48 – 1.6kV
|
150 – 275VAC
200 – 350VDC
|
|
DSD1100
|
100kA / Iimp=10kA
|
480VAC
1.7kVDC
|
150 – 275vAC / 200 – 350VDC
|
|
Critec Range DSD160
|
60kA / Iimp=5kA
|
0.48 – 2kV
|
150 – 440VAC / 200 – 580VDC
|
|
Critec Range DSD140
|
40kA
|
0.48 – 1.8kV
|
150 – 440VAC / 200 – 580VDC
|
|
Critec Range DSD130
|
30kA
|
0.48 – 1.7kV
|
150 – 275VAC / 200 – 350VDC
|
|
Critec Range DSD110
|
10kA
|
0.55 – 1.4kV
|
150 – 440VAC /200 – 580VDC
|
|
Critec Range DSD340, 380
|
40/80kA / Iimp=5/25kA
|
0.85 – 1.7kV
|
275VAC / 350VDC
|
3 Phase
|
TDS/TDS50/DAR/TDS SC – TD suppressor & DINLINE Alarm & Relay Surge Counter
|
10 – 80kA
Iimp= 8 – 16kA
|
600 – 960V
|
275 – 340V
|
|
TDF – Transient Discriminating Filter
|
20ka (L-N, L-G)
10kA (N-G)
|
250 – 600V
|
170 – 340V
|
1 Phase
|
DSF – DINLINE Surge Filter
|
4 – 16kA
|
110 – 750V
|
30 – 275VAC
38VDC
|
1 Phase
|
OHA – Overhead Arrester
|
30kA
|
1.2 – 2kV @15kA
|
150 – 440V
|
|
LPP – Light Pole Protector
|
40kA
|
1.2 – 1.8kV
|
320 – 550V
|
1 Phase
|
UTB – Universal Transient Barrier
|
20kA
|
10 – 480V (L-L)
|
5 – 150VAC
7 – 200VDC
|
|
DSD (DC) SIN Surge Diverter
|
20kA
|
19 – 40V (L-L)
|
15 – 28VDC
|
|
SLP/HSP/DLT – Subscriber/High Speed Line Protection/Termination
|
20kA ([L+L]-E)
Iline= 0.12 – 1A
|
13 – 190V
|
||
RJ11 Telephone Line Protection
|
0.5 – 20kA
|
110V (T-R)
500V ([T-R]-G)
|
280V
|
|
DEP – Data Equipment Protector
|
9 – 15VDC
|
|||
LAN Protector
|
500A
|
23V (L-L)
140V (L-G)
|
Up to 65VDC
|
|
CATV – Community Antenna TV Protector
|
5kA
|
90V
|
||
CCTV – Closed Circuit TV Protector
|
20kA
|
60V
|
||
LCP – Loadcell Protector
|
300A – signal-shield
10kA – shield-ground
|
30V – signal-ground
15V – signal-signal
90V – shield-ground
|
||
TEC/IJP – Transient Earth Clamp & Insulated Joint Protector
|
100kA
|
1000V @ 1kV/µs
|
||
PLF – Power Line Filter
|
20kA
|
50 – 600V
|
275V
|
1 Phase
|
MSPD – Multi-socket Protection Device
|
5kA
|
600V
|
275V
|
1Phase
|
Model
|
Iline
|
Up
|
Surge Rating
|
Phase/Pole
|
PANAMAX MAX 8 – Plug-in Protector
|
15A
|
330V
Telephone – 260V
CATV – 0.7V
Satellite – 27V
|
52kA
|
1 Phase
|
PANAMAX MAX 2
|
15A
|
330 – 700v
Telephone – 260V
CATV – 0.7V
|
52kA
|
1 Phase
|
PANAMAX MAX ImagePro 20 – Digital Equipment Noise Filter
|
20A
|
330V
Telephone – 260V
LAN – 7V
|
52kA
|
1 Phase
|
PANAMAX TowerMAX – Modular Plug-in Protector
|
15A
|
330V
Telephone – 260V
LAN – 7V
T1 – 70V
|
52kA
|
1 Phase
|
For more information and product specifications, please refer to the relevant document link, or contact us on 02 9602 8331 or follow us on Facebook to stay up to date and receive regular updates.